ESD anti-static epoxy flooring
Controlled static dissipation and protection for sensitive electronics. We design to EN IEC 61340-5-1.
ESD floors, commonly called anti-static floors (ESD stands for electrostatic discharge), are conductive or dissipative floors. They carry static charge from people and trolleys away to earth in a controlled way. This page covers poured epoxy ESD systems.
Where a static discharge can destroy semiconductor components, an ESD floor combined with ESD footwear is the usual way to ground people who stand or move about as they work. The requirements are set by the ESD control programme under EN IEC 61340-5-1 or by the contract with your customer. Different rules apply to areas with flammable vapours and dust; we cover them on our ATEX flooring page.
What an anti-static ESD floor is and how it works
Standard epoxy is an electrical insulator: a new coating has a resistance of the order of 10¹² Ω, so static charge builds up on it. A poured ESD floor contains conductive fillers, such as carbon fibres. These usually carry the charge into a conductive intermediate coat, from there into copper tapes, and through the earthing points to earth.
Charge from footwear and wheels
It builds up as people walk and as trolleys roll. It passes into the floor through ESD footwear or conductive wheels.
Conductive layer
Carbon fibres or other conductive fillers carry the charge through the top layer into the conductive intermediate coat, which spreads it across the floor.
Copper tapes
They are bonded to the primed substrate beneath the conductive intermediate coat and connect it to the earthing points.
Earthing point
An electrician connects the earthing points to the building’s earthing system. Their number and layout are set by the system’s technical data sheet or, where needed, by the electrician.
Floor resistance to ground (Rg), classes per ANSI/ESD STM7.1
- Conductive
- ≤ 1×10⁶ Ω
- Fastest dissipation. Chosen when the ESD control programme or your customer requires it.
- Dissipative
- > 1×10⁶ to < 1×10⁹ Ω
- Controlled dissipation. Meets the EN IEC 61340-5-1 limit and is the usual choice for electronics manufacturing, server rooms and laboratories.
- Not suitable for ESD
- ≥ 1×10⁹ Ω
- Does not meet the EN IEC 61340-5-1 limit. Standard new epoxy is of the order of 10¹² Ω, and charge builds up on it.
Where ESD flooring is used
We design the floor build-up around the loads and the requirements of your site.
Electronics manufacturing
SMT lines, component placement and printed circuit board assembly. A component can be destroyed, or left with latent damage, by a discharge a person does not even feel.
Electronics servicing, testing and packing
EN IEC 61340-5-1 covers not only manufacturing but also the servicing, testing, packing and transport of sensitive components.
Server rooms and data centres
Protects servers, network equipment and storage systems from latent discharge damage, especially during installation and servicing.
Laboratories
Workplaces with sensitive measuring and analytical equipment. If the site also needs chemical resistance, a system is chosen that meets both requirements.
Cleanrooms
Used where electronics are handled in a clean environment. Charged surfaces also attract dust.
Areas with flammable vapours and dust
The ESD standard does not deal with explosion protection; it expressly excludes flammable liquids, gases and powders. The employer sets out the measures in a written explosion protection document (in Slovakia under Government Regulation No. 393/2006 Coll.), and the floor’s resistance is assessed under different rules. We cover them on our ATEX flooring page.
Standards and regulations
The regulations, standards and technical rules the floor is designed and tested to. The properties of the materials used are documented by the manufacturer in the technical data sheet and the declaration of performance.
The benefits of ESD flooring
Controlled charge dissipation
We design the build-up for a resistance to ground below 1×10⁹ Ω to EN IEC 61340-5-1, or for a narrower range if your ESD control programme or your customer requires one.
Continuous, joint-free surface
Unlike tiles, a poured floor has no grout lines for dust to settle in. It also suits clean production areas.
Conductive through the whole layer
The conductive fillers run through the whole layer, but resistance is affected by dirt, film-forming cleaning and care products, humidity and wear. That is why it needs to be measured regularly.
Verified by measurement
The finished floor’s resistance to ground is verified by measurement to IEC 61340-4-1. The test report serves as evidence for the audit of your ESD control programme. Who carries out the measurement is agreed in the quote.
The quote sets out the full build-up of the ESD system as per the manufacturer’s technical data sheet, including copper tapes and earthing points. Connection to the building’s earthing system (done by an electrician), resistance measurement and the test report are also agreed in the quote. The exact price depends on the area, the condition of the substrate, the system chosen and whether you need a dissipative or a conductive floor.
Request a quote+421 948 143 981obchod@epoxidovo.skFrequently asked questions
ESD flooring: the questions that come up most often in design and installation.
How long does an ESD floor last, and how often should it be tested?
What is the difference between a dissipative and a conductive floor?
What footwear should be worn on an ESD floor?
How is an ESD floor tested?
What is the difference between a poured ESD floor and ESD vinyl or tiles?
Can an ESD floor also be anti-slip or chemical-resistant?
How long does installation take?
How do you clean and maintain an ESD floor?
How much does an anti-static (ESD) floor cost?
More specialist flooring
For an overview of all our systems for businesses and production, see industrial flooring.
A dissipative floor below 10⁸ Ω that, together with dissipative footwear, drains static charge from people in explosive atmospheres.
A seamless, easy-to-clean surface in line with the flooring requirements of Annex II to Regulation (EC) No 852/2004.
We recommend an R rating to suit your premises. Slip resistance is determined by the ramp test (DIN 51130 / DIN EN 16165).
Need ESD flooring?
We confirm the price after a site survey. The survey and the quote are both free and without obligation.