ESD anti-static epoxy flooring

Controlled static dissipation and protection for sensitive electronics. We design to EN IEC 61340-5-1.

Price on request

ESD floors, commonly called anti-static floors (ESD stands for electrostatic discharge), are conductive or dissipative floors. They carry static charge from people and trolleys away to earth in a controlled way. This page covers poured epoxy ESD systems.

Where a static discharge can destroy semiconductor components, an ESD floor combined with ESD footwear is the usual way to ground people who stand or move about as they work. The requirements are set by the ESD control programme under EN IEC 61340-5-1 or by the contract with your customer. Different rules apply to areas with flammable vapours and dust; we cover them on our ATEX flooring page.

What an anti-static ESD floor is and how it works

Standard epoxy is an electrical insulator: a new coating has a resistance of the order of 10¹² Ω, so static charge builds up on it. A poured ESD floor contains conductive fillers, such as carbon fibres. These usually carry the charge into a conductive intermediate coat, from there into copper tapes, and through the earthing points to earth.

Cross-section of the floor: charge from footwear and trolley wheels passes through the conductive layer into the copper tapes and via the earthing point to earth1234
  1. Charge from footwear and wheels

    It builds up as people walk and as trolleys roll. It passes into the floor through ESD footwear or conductive wheels.

  2. Conductive layer

    Carbon fibres or other conductive fillers carry the charge through the top layer into the conductive intermediate coat, which spreads it across the floor.

  3. Copper tapes

    They are bonded to the primed substrate beneath the conductive intermediate coat and connect it to the earthing points.

  4. Earthing point

    An electrician connects the earthing points to the building’s earthing system. Their number and layout are set by the system’s technical data sheet or, where needed, by the electrician.

Floor resistance to ground (Rg), classes per ANSI/ESD STM7.1

Conductive
Dissipative
Not suitable for ESD
Conductive
≤ 1×10⁶ Ω
Fastest dissipation. Chosen when the ESD control programme or your customer requires it.
Dissipative
> 1×10⁶ to < 1×10⁹ Ω
Controlled dissipation. Meets the EN IEC 61340-5-1 limit and is the usual choice for electronics manufacturing, server rooms and laboratories.
Not suitable for ESD
≥ 1×10⁹ Ω
Does not meet the EN IEC 61340-5-1 limit. Standard new epoxy is of the order of 10¹² Ω, and charge builds up on it.

Where ESD flooring is used

We design the floor build-up around the loads and the requirements of your site.

Electronics manufacturing

SMT lines, component placement and printed circuit board assembly. A component can be destroyed, or left with latent damage, by a discharge a person does not even feel.

Electronics servicing, testing and packing

EN IEC 61340-5-1 covers not only manufacturing but also the servicing, testing, packing and transport of sensitive components.

Server rooms and data centres

Protects servers, network equipment and storage systems from latent discharge damage, especially during installation and servicing.

Laboratories

Workplaces with sensitive measuring and analytical equipment. If the site also needs chemical resistance, a system is chosen that meets both requirements.

Cleanrooms

Used where electronics are handled in a clean environment. Charged surfaces also attract dust.

Areas with flammable vapours and dust

The ESD standard does not deal with explosion protection; it expressly excludes flammable liquids, gases and powders. The employer sets out the measures in a written explosion protection document (in Slovakia under Government Regulation No. 393/2006 Coll.), and the floor’s resistance is assessed under different rules. We cover them on our ATEX flooring page.

Standards and regulations

The regulations, standards and technical rules the floor is designed and tested to. The properties of the materials used are documented by the manufacturer in the technical data sheet and the declaration of performance.

EN IEC 61340-5-1:2024
Requirements for an ESD control programme for work with electrical and electronic parts, assemblies and equipment. For flooring it specifies a resistance to ground below 1×10⁹ Ω. Where the floor and footwear together ground people, the person/footwear/flooring system must have a resistance below 1×10⁹ Ω and a body voltage below 100 V when walking. It does not apply to electrically initiated explosive devices or to flammable liquids, gases and powders.
EN 61340-4-1 (IEC 61340-4-1)
Test method for measuring the electrical resistance of floor coverings and installed floors. It sets no limits; those are in EN IEC 61340-5-1.
IEC 61340-4-5
Test method for the person/footwear/flooring system: resistance from body to ground and body voltage when walking (the walking test).
ANSI/ESD STM7.1
US test method for flooring. It classes a floor with a resistance to ground of no more than 1×10⁶ Ω as conductive, and one above 1×10⁶ Ω and below 1×10⁹ Ω as dissipative.
EN 1081
Test method for measuring the vertical resistance, resistance to ground and surface resistance of resilient, laminate and modular floor coverings. It sets no limits. Manufacturers of poured floors use it to state resistance to ground, mainly for explosion protection.
Directive 1999/92/EC; in Slovakia, Government Regulation No. 393/2006 Coll.
For explosion protection, the floor is not assessed under the ESD standard. As part of explosion prevention, the employer must also take electrostatic discharge into account and must demonstrate the measures taken in a written explosion protection document. See our ATEX flooring page for details.

The benefits of ESD flooring

Controlled charge dissipation

We design the build-up for a resistance to ground below 1×10⁹ Ω to EN IEC 61340-5-1, or for a narrower range if your ESD control programme or your customer requires one.

Continuous, joint-free surface

Unlike tiles, a poured floor has no grout lines for dust to settle in. It also suits clean production areas.

Conductive through the whole layer

The conductive fillers run through the whole layer, but resistance is affected by dirt, film-forming cleaning and care products, humidity and wear. That is why it needs to be measured regularly.

Verified by measurement

The finished floor’s resistance to ground is verified by measurement to IEC 61340-4-1. The test report serves as evidence for the audit of your ESD control programme. Who carries out the measurement is agreed in the quote.

Price on request

The quote sets out the full build-up of the ESD system as per the manufacturer’s technical data sheet, including copper tapes and earthing points. Connection to the building’s earthing system (done by an electrician), resistance measurement and the test report are also agreed in the quote. The exact price depends on the area, the condition of the substrate, the system chosen and whether you need a dissipative or a conductive floor.

Request a quote+421 948 143 981obchod@epoxidovo.sk

Frequently asked questions

ESD flooring: the questions that come up most often in design and installation.

How long does an ESD floor last, and how often should it be tested?
Service life depends on the thickness of the system and on how the floor is used: a thin ESD coating will not last as long as a thicker self-levelling layer. Resistance can change without any visible damage, for example because of dirt or a different cleaning product. We therefore recommend a check measurement at least once a year and after every change to the cleaning routine. The binding interval is set by the compliance verification plan in your ESD control programme.
What is the difference between a dissipative and a conductive floor?
Conductive and dissipative floors differ in their resistance to ground. Under ANSI/ESD STM7.1, a conductive floor has no more than 1×10⁶ Ω, a dissipative floor more than 1×10⁶ Ω and less than 1×10⁹ Ω. For electronics manufacturing, server rooms and laboratories a dissipative floor is usually enough, because EN IEC 61340-5-1 requires a resistance below 1×10⁹ Ω. The deciding factor, though, is a test of the whole system with the footwear your staff wear. A conductive floor is chosen when the ESD control programme or your customer requires it. Different rules apply to explosive atmospheres; we cover them on our ATEX flooring page.
What footwear should be worn on an ESD floor?
ESD footwear is worn on an ESD floor; its sole carries charge away into the floor. What matters is the whole person/footwear/flooring system: under EN IEC 61340-5-1 its resistance to ground must be below 1×10⁹ Ω, and the body voltage in the walking test to IEC 61340-4-5 must be below 100 V. The test is therefore carried out with the footwear your staff actually wear. In practice, footwear is checked on a tester, usually daily on entering the ESD protected area (EPA).
How is an ESD floor tested?
The finished floor’s resistance to ground is measured to IEC 61340-4-1 with a 2.5 kg electrode at several points across the floor. Where the floor grounds people, the resistance of the person/footwear/flooring system and the body voltage when walking are also measured, to IEC 61340-4-5. Air humidity, the cleanliness of the floor and the footwear all affect the result, so the conditions are recorded along with the measurement.
What is the difference between a poured ESD floor and ESD vinyl or tiles?
Both solutions can meet the EN IEC 61340-5-1 limit, and in both cases it is the measurement of the finished floor that counts. A poured epoxy floor is continuous, with no joints between sheets or tiles, and is applied directly to the prepared concrete substrate. ESD vinyl and tiles have joints and are either bonded with conductive adhesive or loose-laid. The choice depends on the loading, the condition of the substrate and the cleaning method. We install poured epoxy systems.
Can an ESD floor also be anti-slip or chemical-resistant?
Yes, if the chosen system allows it. Slip resistance matters, for example, in areas that are wet-cleaned, and chemical resistance in laboratories. We choose a system for which the manufacturer declares all the required properties together. For example, the technical data sheet for the matt ESD seal coat Sikafloor-305 W ESD gives a slip resistance rating of R11 to DIN 51130. The rating applies to the build-up the manufacturer tested. We explain the R ratings on our anti-slip flooring page.
How long does installation take?
Installation time depends on the area, the condition of the substrate and the system chosen. There are several stages: preparing and priming the substrate, fitting the earthing points and copper tapes, the conductive intermediate coat, the ESD top layer and the measurement. The waiting times in the technical data sheet must be observed between layers. We agree the schedule after the site survey.
How do you clean and maintain an ESD floor?
Clean an ESD floor in line with the system manufacturer’s instructions. Do not use film-forming polishes, matting agents or extra “cosmetic” coatings that are not part of the ESD system. They impair the conductivity of the surface and can push the floor’s resistance above the limit. After changing the cleaning product or after a repair, we recommend measuring the resistance again.
How much does an anti-static (ESD) floor cost?
We price each project individually. The price depends mainly on the area and the condition of the substrate, on the system chosen (a thin ESD coating or a thicker self-levelling layer), on the number of earthing points and on whether you need a dissipative or a conductive floor. You can send us your enquiry through the quote form.

Need ESD flooring?

We confirm the price after a site survey. The survey and the quote are both free and without obligation.